The function of magnetic assistant matrix and option matrix is added to JYR 20E Transformer heat run tester on the base of JYR DC Resistance Tester (20D)、(40D,), the wiring is simplified, the magnetic assistant and option items can be finished by one time of wiring. The demagnetization function is added, and the residual magnetism of the transformer after contentment is reduced. The DC resistance measuring range is extended from the original 0~130 Ω to 0~40 kΩ. The instrument also can measure the resistance of the transformers and instrument transformer with high resistance, to realize one instrument with multiple usages.
Function Introduction
● JYR 20E Transformer heat run tester is suitable for DC resistance test and heat run test of 240MVA and below transformers.
● With the third constant current source technology, the measuring rang is from 0 to 40 kΩ.
● Operated by touching the colorful screen, the operation is more simple.
● The two channels can be tested simultaneously.
● JYR 20E Transformer heat run tester with function of magnetic assistant matrix and option matrix
● With the function of residual magnetism.
● The accuracy is improved, the minimum resolution can reach 0.01 µΩ.
● The interval time during the heat run test is 10s, 30s and 60s for option.
● Automatic print timing.
● The data can be stored automatically and timing.
● The U disc interface make the data can be exported to the computer for forming the temperature rise curve.
● With the RS485 communication interface, the instrument can be operated by the computer.
● JYR 20E Transformer heat run winding resistance tester With the temperature rise test software, the data can be processed automatically.
● With the anti-arcing protection function for the inductive tested products.
● With AC380V mis-connection protection function.
● With the discharging alarm by sound and the discharging indicating clearly function.TECHNICAL SPECIFICATION:
Type
20E
40E
Output current
20A, 10A, 3A, 1A, 0.3A, 25mA
40A, 20A, 10A, 3A, 1A, 0.3A, 25mA
Range
0~40 kΩ
0~40 kΩ
Accuracy
0.2%±0.2 µΩ
0.2%±0.2 µΩ
Min. Resolution
0.1 µΩ
0.01 µΩ
Output voltage
DC50V
Timing of heat run
10s, 30s, 60s for option
Operation power
AC220V±10%, 50 Hz±1Hz
Operation temperature
-20℃~40℃
Relative humidity
≤80%RH, no dew
Volume
L445mm * W370mm * H210mm
Net weight
15.7 kg