News

Test time requirements of HV switchgear dynamic characteristics tester

High voltage switch dynamic characteristics tester Circuit Breaker Analyzer(CB analyzer) is widely used for Circuit Breaker timing test,CB timing test,switching characteristic test of SF6 switchgear, GIS combination of electrical, vacuum switch, oil switch and column switches, contacts and so on.

The specific test requirements and times are as follows:

1. Measurement time: not less than the circuit breaker closing time, the resolution is 0.01ms;

2. Time measurement error: 0.1ms within 200ms±, ±2% above 200ms;

3. Synchronization time measurement error: the synchronization time of the tester is not more than ±0.1ms;

4. When measuring the closing and opening time of the circuit breaker, the trigger time difference between the closing power supply and the opening power supply should be set:

Opening and closing time S1 = closing time + no current gap time closing time

Closing time S2 = closing time + short opening time of gold

Among them, the door opening time and closing time are measured in advance. No current gap and metal short circuit time are provided by the high-voltage switch manufacturer, and the setting time should be slightly less than the specified value (if the standard without current gap time is 300ms, it can be set) about 280 ms; If the metal short-circuit time is 60 ms, it can be set to about 50 ms).

High voltage switch dynamic characteristics tester test data analysis and processing

1. The test results should be compared with the values given in the circuit breaker manual, and should meet the requirements of the manufacturer;

2. If there is test data in the test project that does not meet the manufacturer's requirements, first check whether the wiring situation, parameter settings, and instrument conditions meet the test requirements;

3. When the opening time does not meet the requirements of the specification, the possible reasons are: first, the position of the opening electromagnet jackrod and the opening switch is not suitable; The second is tired of opening the spring; Third, the opening distance or overtravel does not meet the requirements. According to the manufacturer's technical requirements, adjust the opening electromagnet, opening and closing spring and mechanism linkage;

4. When the closing time does not meet the requirements of the specification, the possible reasons are: first, the single opening and closing time does not meet the requirements of the specification; Second, the circuit breaker operating mechanism has tripping performance. Comprehensively analyze the above reasons, adjust the single opening and closing time or adjust the release according to the manufacturer's technical requirements;

5. When the values in different periods do not meet the requirements of the specification, the possible reasons are: first, the three-phase opening distance is inconsistent; Second, the electromagnet action time of the splitting mechanism is inconsistent. The above reasons should be comprehensively analyzed, and the opening electromagnet, opening and closing spring, and mechanism connecting rod should be adjusted according to the manufacturer's technical requirements.