110kV/220kV Substation Series Testers

  • 200A Contact Resistance Tester  (JYL-200B/100B )
200A Contact Resistance Tester  (JYL-200B/100B )

200A Contact Resistance Tester (JYL-200B/100B )

  • Max.output current: 200A
  • Max.test rang: 0.01μΩ~100mΩ
  • Automatically deduct grounding resistance data
  • Automatic shielding test line resistance
  • Product description: JYL-200B/100B contact resistance tester can measure contact resistance of high voltage switch and circuit breaker, also can test primar side resistance of transformer and grounding wire in groups.
  • INQUIRY


What is contact resistance and why should it be measured regularly?

Contact resistance refers to the resistance encountered by current as it passes through the contact surfaces between two conductors. The magnitude of this resistance mainly depends on the smoothness of the contact surface, contact pressure, and material properties. In electrical equipment, particularly in high-voltage switches and circuit breakers, contact resistance has a significant impact on the normal operation of the equipment.

The measurement of contact resistance is carried out to ensure the reliable operation of electrical equipment. Over time, contact points may experience oxidation, corrosion, or wear, which can increase resistance, leading to overheating, reduced conductivity, and even safety risks. By regularly measuring contact resistance, the condition of the contact points can be assessed, preventing overheating damage, improving the equipment’s conductivity and safety, and enabling preventive maintenance. This helps to identify and address potential issues in advance, ensuring the stable operation of the power system.


JYL100B/200B has a maximum output current of up to 200A, with a measurement range of 0Ω to 100mΩ. It is lightweight and offers precise testing (±0.2μΩ), utilizing the Kelvin four-wire measurement method to effectively eliminate the influence of the test leads' resistance on the results. This instrument is suitable for measuring the contact resistance of circuit breakers, disconnectors, grounding switches, transformers, busbars, high-voltage switchgear, and grounding conductors. It features high output voltage and extended duration, allowing for continuous long-term measurement. Additionally, it can measure the primary resistance of current transformers and perform group measurements of grounding wires



JYL100B/200B Technical Features:

1.The Max. test current can reach 200A which can test Min.0.01μΩ contact resistance value

2.With high output voltage, the test line is easy to carry and connection

3.The test output current is from high accuracy switch type constant-current source, no manual adjustment required, which will shorten test time and improves test accuracy.

4.Adopts Kevin four-pole wiring method to eliminate the effect of test wire resistance to test results effectively.

5.The current compensation function is added, which effectively reduces the influence of the current shunt of the double-ended ground wire of the GIS switch on the test results.

6.With overheat protective circuit which can ensure the instrument is reliable and stable during long time continuous work

7.The instrument is simple in operation. With a light weight, it is suitable for outdoor work.

8. With RS485 communication interface for remote control measurement(with operation software) .

9. With U disk storage interface and built-in printer.


TECHNICAL PARAMETERS:

Figures on display

Four and half figure display

Type

100B

200B

Output current

50A

100A

50A

100A

200A

Test range

0~100mΩ

0~50mΩ

0~100mΩ

0~50mΩ

0~20mΩ

Accuracy

0.5% ± 0.2μΩ

Minimum resolution

0.01μΩ

Output voltage

DC 10V

Power supply in operation

AC220V±10%,50Hz

Temperature in operation

-20 ~40℃

Relative humidity

80%RH,  No dew

Volume

Length 360mm x Width 235mm x Height 270mm

Net weight

8.5 kg



JYL100B/200B Main Application Object Range: