TECHNICAL INTRODUCTION:
KRI 9310 transformer winding resistance tester transformer winding resistance meter is suitable for small distribution transformer (below 80KVA)
KRI 9310 transformer winding resistance meter is provided with the temperature conversion function. By selecting test sample material(copper/aluminum) and temperature from tester, the instrument can be able to automatically convert them to the resistance values under the standard temperature (20℃,75℃,120℃).
KRI 9310 DC transformer winding resistance meter is provided with the data storage function, 500 groups of experimental data can be stored within the instrument.
also KRI 9310 transformer winding resistance meter has USB interface, the data can be down load to flash disc
TECHNOLOGY SPECIFICATION:
Tester type |
KRI 9310 transformer winding resistance meter |
|||||
Scope of application |
10A |
3A |
1A |
0.3A |
0.1A |
5mA |
Test range |
0Ω~0.1Ω |
0.01Ω~2Ω |
0.03Ω~6Ω |
0.1Ω~20Ω |
0.3Ω~60Ω |
30Ω~20KΩ |
Accuracy |
0.1%±0.5μΩ |
|||||
Minimum resolution |
0.1μΩ |
|||||
Built in battery |
11.1V ; Capacity:4500mmAh |
|||||
Standard conversion temperature |
20℃/75℃/120℃ |
|||||
Temperature test range |
-99.9~199.9℃ ; Accuracy: ±0.5% (JYR9311 only) |
|||||
Volume |
Length 155mm Width 210mm Height 68mm |
|||||
Net weight |
1.66KGS |