Tech Blogs

Acceptance Criteria for Testing New and Remanufactured Transformers


Testing is the cornerstone of ensuring transformer reliability and a key bridge connecting transformer theoretical design and operational safety. For new transformers, rigorous factory testing ensures that the equipment meets the nameplate specifications and can withstand the test of long-term operation. For refurbished or remanufactured, the focus of testing shifts to diagnostic verification — confirming that the iron core and windings are intact, and that the refurbishment process has successfully restored the equipment's integrity to near-original standards.
Naturally, testing must comply with strict standards. Currently, IEEE C57.12.00 and IEEE C57.12.90 are the main standards for liquid-immersed distribution transformers, power transformers, and voltage-regulating transformers. IEEE C57.12.01 and IEEE C57.12.91, on the other hand, regulate dry-type distribution transformers and power transformers. These standards define "routine tests" (required for each piece of equipment), "design tests" (used to verify model design), and "other tests" (customer-specific tests). Understanding these classifications is crucial for engineers to ensure that the selected transformer — whether new or refurbished — can withstand the expected load without premature failure.

Standard Test Checklist for New and Refurbished Transformers:

Test Items

Remanufactured

(All Types)

New 600V

Dry

New MV

Dry

New Dist.

Liquid

New Class I

Power Sub

Turns Ratio (TTR)

Required

Required

Required

Required

Required

Winding Resistance

Required

≥ 300 kVA

≥ 300 kVA

> 2500 kVA

Required

Impedance & Load Loss

Required

Required

Required

Required

Required

Polarity & Phase Relation

Required

Required

Required

Required

Required

No-Load Loss & Excitation

Required

Required

Required

Required

Required

Applied Voltage (Hipot)

Optional

Required

Required

Required

Required

Induced Voltage

Optional

Required

Required

Required

Required

Insulation Res. (Megger)

Required

≥ 300 kVA

≥ 300 kVA

Required

Required

Insulation Power Factor

Optional

Optional

Optional

Optional

Required

Lightning Impulse

Optional

Design Test

Design Test

Design Test

Required

Pressure & Leak Test

Required

N/A

N/A

Required

Required

Oil Analysis (DGA)

Optional

N/A

N/A

Optional

Required



1. Turns Ratio Test (TTR)

 Measures the voltage ratio between transformer windings to verify compliance with nameplate values and design specifications.

Significance: Validates correct winding turns, detects inter-turn short circuits or tap switch faults, and is mandatory for factory acceptance and post-overhaul checks.

Standard Range:

- Power transformers: Ratio deviation typically ≤ ±0.5% (IEC 60076);

- Distribution transformers: Generally ≤ ±1%.

2. Winding Resistance

Measures the DC resistance of each phase winding to reflect conductor material, cross-sectional area, and joint contact conditions.

Significance: Detects broken strands, loose connections, or inter-turn short circuits in windings.

Standard Range:

- Three-phase unbalance: 2% for distribution transformers, 1% for power transformers;

- Deviation from factory values: Generally ≤ ±2%.

3. Impedance Voltage and Load Loss

Impedance voltage is the voltage applied to the primary winding when the secondary is shorted to achieve rated current; load loss is the active power loss under this condition.

Significance: Evaluates load capacity, efficiency, and short-circuit withstand capability, and is a key indicator for energy efficiency classification.

Standard Range:

- 10kV distribution transformers: Load loss meets IEC60076 energy efficiency requirements;

- Large power transformers: Impedance voltage deviation typically ≤ ±10%.

4. No-Load and Phase Relationship

No-load loss is the active power loss when the secondary is open; no-load current is the excitation current under this condition; phase relationship verifies winding polarity and connection group designation.

Significance: Assesses core quality, detects local overheating, and ensures phase consistency for parallel operation.

Standard Range:

- No-load current: 2% of rated current for distribution transformers;

- Connection group designation must match the nameplate.

5. No-Load Loss and Excitation Current

No-load loss refers to hysteresis and eddy current losses in the core under alternating magnetic fields; excitation current is the current required to maintain core magnetization.

Significance: Reflects core material performance and manufacturing quality, and is a core indicator for energy efficiency assessment.

Standard Range:

- Energy efficiency Level 1 distribution transformers: No-load loss reduced by ~30% compared to standard models;

- Excitation current: Generally 1%3% of rated current.

6. Applied Voltage Test

Applies a specified power frequency AC voltage between windings and ground for a defined duration.

Significance: Verifies the ability of main insulation to withstand power frequency overvoltages and validates insulation strength.

Standard Range:

- 10kV transformers: Applied voltage 35kV/1min (IEC60071);

- 35kV transformers: Applied voltage 80kV/1min(IEC60071).

7. Induced Voltage Test

Applies a voltage higher than the rated value across windings by increasing the power frequency to assess longitudinal insulation (inter-turn, layer-to-layer) strength.

Significance: Detects inter-turn insulation defects to prevent short circuits during operation.

Standard Range:

- Induced voltage: Typically 2× rated voltage;

- Duration: Adjusted by frequency, generally 60s.

8. Impulse Voltage Test

Simulates lightning overvoltages by applying standard waveform impulse voltages (e.g., 1.2/50μs) to the transformer.

Significance: Validates the ability of winding insulation to withstand lightning overvoltages, a critical test for high-voltage transformers.

Standard Range:

- 110kV transformers: Full-wave impulse voltage 480kV(IEC60071);

- 220kV transformers: Full-wave impulse voltage 950kV (IEC60071).


9. Insulation Resistance (Megger)

Measures insulation resistance between windings-to-ground and phase-to-phase using a megohmmeter to reflect moisture, contamination, or degradation of insulation materials.

Significance: Quickly assesses overall insulation health and is the primary test in preventive maintenance.

Standard Range:

- Transformers 35kV: Insulation resistance 300MΩ (20);

- Absorption ratio R60/R15 1.3, polarization index 1.5.

10. Insulation Power Factor

Measures the dielectric loss tangent (tanδ) of insulation to reflect aging, moisture, or local defects in dielectric materials.

Significance: Evaluates overall dielectric performance and is more sensitive than insulation resistance to early-stage degradation.

Standard Range:

- New transformers: tanδ ≤0.5% (20);

- In-service transformers: tanδ ≤1.0%, with no significant increase from historical values.

11. Temp Rise Test

Measures temperatures of windings, core, and oil under rated load to calculate the temperature rise above ambient conditions.

Kingrun Transformer Instrument Co.,Ltd.

kingrun company in exhibition show 2025

kingrun company office building and show room

global clients of kingrun transformer instrument



More Transformer Testers from Kingrun

kingrun series transformer testers