Technology Literature

How to correctly measure the contact resistance of a switchgear?

The principle of measuring the contact resistance of switches
Contact resistance is defined as the ratio of the voltage across the contacts to the current flowing through a pair of closed contacts. It obeys Ohm's law. There is an interface between Metal 1 and Metal 2. The current I from the current source flows through this interface and can be read from an ammeter. The voltage drop across the interface can then be read as U from a voltmeter. The contact resistance value Rx can then be calculated.

Rx=U/I

Since the contact resistance varies with the environment and the passage of current, the measurement conditions should be close to the usage conditions. Accurate measurement must use four-terminal measurement technology and thermal EMF elimination technology. This indirect measurement method can be used to measure contact resistance or loop resistance. It requires three test points, three steps, and three formulas. This method has been proven correct and can also be used to calibrate loop resistance standards.

Typical Methods of Contact Resistance Testing
Four-wire (Kelvin) DC voltage drop is a typical method for contact resistance testing with microohm meters, which ensures a more accurate measurement by eliminating both its own contact resistance and the resistance of the test leads.

Contact resistance testing uses two current connections for injection and two potential leads for voltage drop measurement; the voltage cable must be as close as possible to the connection to be tested and always within the circuit formed by the connected current leads.

Based on the measurement of the voltage drop, a microprocessor-controlled micro-ohmmeter calculates the contact resistance while eliminating errors that can arise from the effect of thermal EMF in the connection (a thermal EMF is a small thermocouple voltage created when two dissimilar metals are connected together) they will be added to the measured total voltage drop, and if they are not subtracted from the measurement by different methods (polarity inversion and averaging, direct measurement of thermal EMF amplitude, etc.), errors will be introduced into the contact resistance test.


If a low resistance reading is obtained when testing the circuit breaker contact resistance with a low current, it is recommended to retest the contacts at a higher current. Why would we benefit from using higher current? A higher current will be able to overcome connection problems and oxidation on the terminals, under these conditions a lower current may produce erroneous (higher) readings.


It is important to maintain consistent measurement conditions in contact resistance testing to be able to compare with previous and future results for trend analysis. Therefore, when taking periodic measurements, the contact resistance test must be performed in the same location, with the same test leads (always use the manufacturer's calibration cable) and under the same conditions to be able to know when to connect, connect, solder or The device will become insecure.



The test items are required for 110kV/220kV substation acceptance and maintenance testing(with corresponding tester types):

Test Object

Testing Item

Tester Type

Cable

Cable AC Hipot Testing

JYCX

Details

Cable Insulation Resistance Testing

JYM KYORITSU

Details

Transformer

Insulation Resistance of Winding

JYM KYORITSU

Details

DC Leakage Testing in 1min

JYDHV

Details

Winding Resistance Testing

JYR50S

Details

Winding Deformation Testing

JYP

Details

Turns Ratio Testing

JYT-A

Details

AC Hipot Testing

JYCX

Details

Short Circuit Impedance Testing

JYW6300

Details

Dan Delta Testing

JYC

Details

Oil Breakdown Voltage (BDV)Testing

JY6611

Details

Oil Tan Delta Testing

GTD-61A

Details

Switchgear

Circuit Breaker/Disconnector Resistance

JYL-200B

Details

Relay

Relay Performance

JY7003G

Details

On-load

On-load Switchgear Testing

JYK-I

Details

Tap Changer Dynamic Testing

JYK-I

Details

Instrument   Transformer

Current Transformer (CT)Testing

JYH-C

Details

Potential Transformer (PT)Testing

JYH-C

Details

Surge Arrestor

Zinc Oxide Characteristics Testing

JY6800

Details

1mA DC Reference Voltage

JYDHV

Details

Capacitor

Capacitor Current

JY6700

Details

Capacitor Inductance

JY6700

Details

Ground Grid

Grounding Down Lead Earth

JYD

Details


Related Articles:

What Test Items are Required for 110kV/220kV Substation Acceptance and Maintenance Testing?

What Tests Must be Done before the Transformer Leaves the Factory?

Main Factors Affecting the Operating Life of Transformers

What is the Purpose of Measuring the DC Resistance of the Transformer Winding?

Points to note in transformer oil breakdown voltage (BDV) test

DC winding resistance tester with 500 times tests on a single charge -JYR9310